Tank Level, Volume and Hydrostatic Pressure

Chemical, sludge and wet well levels are often measured as pressure and then shown as a level or volume. The first tool turns a level into gallons for common tank shapes. The second turns a pressure reading into a level, corrected for specific gravity and the sensor mounting height.

Tank Level to Volume

Formula

Rectangular:          V, ft³ = L x W x level
Vertical cylinder:    V, ft³ = 3.1416 x D² / 4 x level
Horizontal cylinder:  V, ft³ = L x [R² x acos((R - h) / R) - (R - h) x square root of (2Rh - h²)]
                      (R = D / 2, h = level, acos in radians)
Gallons = ft³ x 7.48
Inputs used
  • Tank shape
  • Liquid level (from the tank bottom) (ft)
  • Length (rectangular or horizontal cylinder) (ft)
  • Width (rectangular) (ft)
  • Diameter (cylinders) (ft)
  • Full height (optional, rectangular or vertical cylinder) (ft)

Worked example (fictional plant data)

  1. Horizontal ferric chloride tank, 8 ft diameter, 20 ft long, level 3 ft
  2. Segment area = 4² x acos(1 / 4) - 1 x square root of (2 x 4 x 3 - 3²) = 21.090 - 3.873 = 17.217 ft²
  3. Volume = 17.217 x 20 x 7.48 = 2,576 gal
  4. Full = 3.1416 x 8² / 4 x 20 x 7.48 = 7,520 gal, so 34.3% full

Hydrostatic Pressure to Level

Formula

Water column, ft = Pressure x (Pa per unit) / 2,988.98
   (1 psi = 2.307 ft = 27.68 in of water at 39.2 °F)
Liquid above sensor, ft = Water column, ft / Specific gravity
Level = Liquid above sensor + Sensor height above bottom
Inputs used
  • Pressure at the sensor (gauge)
  • Pressure unit
  • Specific gravity of the liquid
  • Sensor height above the tank bottom (optional) (ft)

Worked example (fictional plant data)

  1. Digester level sensor reads 5.2 psi, sludge SG 1.02, sensor 0.5 ft above the floor
  2. Water column = 5.2 x 2.3067 = 11.995 ft
  3. Sludge above sensor = 11.995 / 1.02 = 11.760 ft
  4. Level = 11.760 + 0.5 = 12.26 ft

Cautions

  • Horizontal tanks with dished or hemispherical heads hold more than flat ends. Use the manufacturer strapping chart when you have one.
  • Specific gravity changes with chemical strength and temperature, and sludge SG with solids. Update the SG in the transmitter when the product changes.
  • A pressure sensor in a vented tank reads gauge pressure. In a closed or pressurized tank, use a DP transmitter to cancel the head space pressure.
  • Never enter a tank or wet well to service a sensor without following your confined space program.